Siemens CU240B-2 Parameter Manual page 306

Table of Contents

Advertisement

Parameters
List of Parameters
p2251
Technology controller mode / Tec_ctrl mode
Access level: 3
Can be changed: T
Units group: -
Min
0
Description:
Sets the mode for using the technology controller output.
Value:
0:
1:
Dependency:
p2251 = 0, 1 is only effective if the enable signal of the technology controller is interconnected (p2200 > 0).
p2253[0...n]
CI: Technology controller setpoint 1 / Tec_ctrl setp 1
Access level: 2
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for the setpoint 1 of the technology controller.
Dependency:
Refer to: p2254, p2255
p2254[0...n]
CI: Technology controller setpoint 2 / Tec_ctrl setp 2
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for the setpoint 2 of the technology controller.
Dependency:
Refer to: p2253, p2256
p2255
Technology controller setpoint 1 scaling / Tec_ctrl set1 scal
Access level: 3
Can be changed: U, T
Units group: -
Min
0.00 [%]
Description:
Sets the scaling for the setpoint 1 of the technology controller.
Dependency:
Refer to: p2253
p2256
Technology controller setpoint 2 scaling / Tec_ctrl set2 scal
Access level: 3
Can be changed: U, T
Units group: -
Min
0.00 [%]
Description:
Sets the scaling for the setpoint 2 of the technology controller.
Dependency:
Refer to: p2254
1-306
Technology controller as main speed setpoint
Technology controller as supplementary speed setpoint
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
100.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
100.00 [%]
Data type: Integer16
Data set: -
Factory setting
0
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
0
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
0
Data type: FloatingPoint32
Data set: -
Factory setting
100.00 [%]
Data type: FloatingPoint32
Data set: -
Factory setting
100.00 [%]