Handling BICO technology
Binector:
r0723.15
Connectors are "analog signals" that can be freely interconnected (e.g. percentage variables, speeds or torques).
Connector:
r0723
Connectors are also "CO:" display parameters (CO = Connector Output).
Parameterization:
At the signal destination, the required binector or connector is selected using appropriate parameters:
"BI:" parameter for binectors (BI = Binector Input)
or
"CI:" parameter for connectors (CI = Connector Input)
Example:
The main setpoint for the speed controller (CI: p1070) should be received from the output of the motorized potentiometer
(CO: r1050) and the "jog" command (BI: p1055) from digital input DI0 (BO: r0722.0, Terminal 5 (Kl.5)) on the CU.
Digital input
1
DI0
Kl.5
r0722.0
[2220]
Motorized potentiometer
Raise
Lower
[3020]
Parameterizing steps:
1
p1055[0] = 722.0
Terminal 5 (Kl.5) acts as "Jog bit 0".
The output of the motorized potentiometer acts as main setpoint for the speed controller.
2
p1070[0] = 1050
1
2
Explanations for the function diagrams
Handling BICO technology
Control bit 8
r0967.8
p1055[C]
722.0
[2501]
2
r1050
3
4
Setpoint
channel
Main setpoint
p1070.[C]
(755[0])
Jog setpoint 1
[3030]
5
FP_1030_97_61.vsd
13.12.2010
Speed controller
6
7
Function diagram
G120 CU240B/E-2
V4.4
8
- 1030 -