p1350[0...n]
Soft starting / Soft starting
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
Sets whether the voltage is continuously increased during the magnetizing phase (p1350 = 1, On) or whether it
jumps directly to the voltage boost (p1350 = 0, Off).
Value:
0:
1:
Note:
The settings for this parameter have the following advantages and disadvantages:
0 = off (jump directly to voltage boost)
Advantage: Flux is established quickly -> torque is quickly available
Disadvantage: The motor can move while it is being magnetized
1 = on (voltage is continually established)
Advantage: The motor is unlikely to rotate
Disadvantage: The flux is established slower -> torque is available later
p1351[0...n]
CO: Motor holding brake starting frequency / Brake f_start
Access level: 3
Can be changed: U, T
Units group: -
Min
-300.00 [%]
Description:
Sets the frequency setting value at the slip compensation output for starting up with motor holding brake.
Dependency:
When setting p1351 > 0, then slip compensation is automatically activated (p1335 = 100 %).
Refer to: p1352
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
Connected with p1352 a value of 100% corresponds to the motor rated slip (r0330).
p1352[0...n]
CI: Motor holding brake starting frequency signal source / Brake f_start
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the frequency setting value at the slip compensation output for starting up with motor
holding brake.
Dependency:
Refer to: p1216
Note:
A value of 100% corresponds to the motor rated slip (r0330).
The setting of the starting frequency begins after magnetizing (see p0346, r0056.4) and ends once the brake open-
ing time (p1216) has elapsed and the starting frequency (p1334) has been reached.
A setting value of zero means that no setting procedure will take place.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
OFF
ON
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
300.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Parameters
List of Parameters
Data type: Integer16
Data set: DDS, p0180
Factory setting
0
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.00 [%]
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
1351[0]
1-195