Siemens CU240B-2 Parameter Manual page 389

Table of Contents

Advertisement

p10106
SI acknowledgement internal event F-DI (processor 2) / SI ackn int evt P2
CU240E-2 DP F
Access level: 3
CU240E-2 F
Can be changed: C(95)
Units group: -
Min
0
Description:
Select a safety-relevant digital input for the signal "acknowledge internal event" (internal fault).
The falling edge at this input resets the status "internal event" in the drive.
Value:
0:
1:
2:
3:
255:
Dependency:
Refer to: p10006
Note:
If value = 0:
No terminal assigned, acknowledge input has a static zero value.
p10117
SI digital inputs debounce time (processor 2) / SI DI t_debounceP2
CU240E-2 DP F
Access level: 3
CU240E-2 F
Can be changed: C(95)
Units group: -
Min
0.00 [ms]
Description:
Sets the debounce time for digital inputs.
The debounce time acts on the following digital inputs:
- Fail-safe digital inputs (F-DI).
- Single-channel digital input 2 (DI 2, read back input for the forced checking procedure).
The debounce time is accepted rounded off to whole milliseconds.
Dependency:
Refer to: p10017
Note:
Example:
Debounce time = 1 ms: Fault pulses of 1 ms are filtered; only pulses longer than 2 ms are processed.
Debounce time = 3 ms: Fault pulses of 3 ms are filtered; only pulses longer than 4 ms are processed.
The debounce result can be read in r10151.
p10122
SI STO input terminal (processor 2) / SI STO F-DI P2
CU240E-2 DP F
Access level: 3
CU240E-2 F
Can be changed: C(95)
Units group: -
Min
0
Description:
Sets the fail-safe digital input (F-DI) for the "STO" function.
Value:
0:
1:
2:
3:
255:
Dependency:
Refer to: p10022
Note:
If value = 0:
No terminal assigned, safety function always active.
If value = 255:
No terminal assigned, safety function always inactive.
F-DI: Failsafe Digital Input
STO: Safe Torque Off
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Statically active
F-DI 0
F-DI 1
F-DI 2
Statically inact
Statically active
F-DI 0
F-DI 1
F-DI 2
Statically inact
Calculated: -
Scaling: -
Unit selection: -
Max
255
Calculated: -
Scaling: -
Unit selection: -
Max
100.00 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
255
Parameters
List of Parameters
Data type: Integer16
Data set: -
Factory setting
0
Data type: FloatingPoint32
Data set: -
Factory setting
1.00 [ms]
Data type: Integer16
Data set: -
Factory setting
0
1-389

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f