Siemens CU240B-2 Parameter Manual page 46

Table of Contents

Advertisement

Parameters
List of Parameters
r0206[0...4]
Rated power unit power / PU P_rated
Access level: 2
Can be changed: -
Units group: 14_6
Min
- [kW]
Description:
Displays the rated power unit power for various load duty cycles.
Index:
[0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = Reserved
[4] = Reserved
Dependency:
IECdrives (p0100 = 0): Units kW
NEMA drives (p0100 = 1): Units hp
Refer to: p0100, p0205
r0207[0...4]
Rated power unit current / PU PI_rated
Access level: 3
Can be changed: -
Units group: -
Min
- [Arms]
Description:
Displays the rated power unit power for various load duty cycles.
Index:
[0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = Reserved
[4] = Reserved
Dependency:
Refer to: p0205
r0208
Rated power unit line supply voltage / PU U_rated
Access level: 2
Can be changed: -
Units group: -
Min
- [Vrms]
Description:
Displays the rated line supply voltage of the power unit.
r0208 = 400 : 380 - 480 V +/-10 %
r0208 = 500 : 500 - 600 V +/-10 %
r0208 = 690 : 660 - 690 V +/-10 %
r0209[0...4]
Power unit, maximum current / PU I_max
Access level: 3
Can be changed: -
Units group: -
Min
- [Arms]
Description:
Displays the maximum output current of the power unit.
Index:
[0] = Catalog
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = Reserved
[4] = Reserved
Dependency:
Refer to: p0205
1-46
Calculated: -
Scaling: -
Unit selection: p0100
Max
- [kW]
Calculated: -
Scaling: -
Unit selection: -
Max
- [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max
- [Vrms]
Calculated: -
Scaling: -
Unit selection: -
Max
- [Arms]
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: FloatingPoint32
Data set: -
Factory setting
- [kW]
Data type: FloatingPoint32
Data set: -
Factory setting
- [Arms]
Data type: FloatingPoint32
Data set: -
Factory setting
- [Vrms]
Data type: FloatingPoint32
Data set: -
Factory setting
- [Arms]
© Siemens AG 2011 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f