Parameters
List of Parameters
r0055.0...15
CO/BO: Supplementary control word / Suppl STW
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays supplementary control word.
Bit field:
Bit
Signal name
00
Fixed setp bit 0
01
Fixed setp bit 1
02
Fixed setp bit 2
03
Fixed setp bit 3
04
DDS select. bit 0
05
DDS select. bit 1
08
Technology controller enable
09
DC braking enable
11
Droop enable
12
Torque control active
13
External fault 1 (F07860)
15
CDS bit 1
Note:
The following control bits are displayed in r0055:
Bit 00: r1198 Bit 0
Bit 01: r1198 Bit 1
Bit 02: r1198 Bit 2
Bit 03: r1198 Bit 3
Bit 04: r0837 Bit 0
Bit 05: r0837 Bit 1
Bit 08: r2349 Bit 0 (negated)
Bit 09: r1239 Bit 11
Bit 11: r1406 Bit 11
Bit 12: r1406 Bit 12
Bit 13: r2138 Bit 13
Bit 15: r0836 Bit 1
1-34
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: Unsigned16
Data set: -
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
Yes
No
© Siemens AG 2011 All Rights Reserved