Faults and Alarms
List of Faults and Alarms
F01033
Units changeover: Reference parameter value invalid
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
When changing over the units to the referred representation type, it is not permissible for any of the required
reference parameters to be equal to 0.0
Fault value (r0949, parameter):
Reference parameter whose value is 0.0.
See also: p0505 (Selecting the system of units), p0595 (Selecting technological units)
Remedy:
Set the value of the reference parameter to a number different than 0.0.
See also: p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004
F01034
Units changeover: Calculation parameter values after reference value change
unsuccessful
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The change of a reference parameter meant that for an involved parameter the selected value was not able to be re-
calculated in the per unit representation. The change was rejected and the original parameter value restored.
Fault value (r0949, parameter):
Parameter whose value was not able to be re-calculated.
See also: p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004
Remedy:
Select the value of the reference parameter such that the parameter involved can be calculated in the per unit
representation.
See also: p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004
A01035 (F)
ACX: Boot from the back-up parameter back-up files
Reaction:
NONE
Acknowledge:
NONE
Cause:
When the Control Unit is booted, no complete data set was found from the parameter back-up files. The last time
that the parameterization was saved, it was not completely carried out. Instead, a back-up data set or a back-up
parameter back-up file is downloaded.
Alarm value (r2124, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
If you have saved the project using the commissioning software, carry out a new download for your project. Save
using the function "Copy RAM to ROM" or with p0971 = 1 so that all of the parameter files are again completely
written to the non-volatile memory.
F01036 (A)
ACX: Parameter back-up file missing
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
When downloading the device parameterization, a parameter back-up file associated with a drive object cannot be
found. Neither a PSxxxyyy.ACX, a PSxxxyyy.NEW nor a PSxxxyyy.BAK parameter back-up file exists in the non-
volatile memory for this drive object.
Fault value (r0949, interpret hexadecimal):
Byte 1: yyy in the file name PSxxxyyy.ACX
yyy = 000 --> consistency back-up file
yyy = 001 ... 062 --> drive object number
yyy = 099 --> PROFIBUS parameter back-up file
Byte 2, 3, 4:
Only for internal Siemens troubleshooting.
Remedy:
If you have saved the project data using the commissioning software, carry out a new download for your project.
Save using the function "Copy RAM to ROM" or with p0971 = 1 so that all of the parameter files are again completely
written to the non-volatile memory.
If you have not saved the project data, then first commissioning of the system has to be carried out again.
3-662
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
© Siemens AG 2011 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents