Siemens CU240B-2 Parameter Manual page 279

Table of Contents

Advertisement

r2124[0...63]
Alarm value / Alarm value
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays additional information about the active alarm (as integer number).
Dependency:
Refer to: r2110, r2122, r2123, r2125, r2134, r2145, r2146
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
r2125[0...63]
Alarm time removed in milliseconds / t_alarm res ms
Access level: 3
Can be changed: -
Units group: -
Min
- [ms]
Description:
Displays the system runtime in milliseconds when the alarm was cleared.
Dependency:
Refer to: r2110, r2122, r2123, r2124, r2134, r2145, r2146
Notice:
The time comprises r2146 (days) and r2125 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
p2126[0...19]
Setting fault number for acknowledge mode / Fault_no ackn_mode
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
Selects the faults for which the acknowledge mode is to be changed
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2127
Notice:
It is not possible to re-parameterize the acknowledge mode of a fault in the following cases:
- if there is no existing fault number.
- the message type is not "fault" (F).
- when a fault is present.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
- [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
65535
Parameters
List of Parameters
Data type: Integer32
Data set: -
Factory setting
-
Data type: Unsigned32
Data set: -
Factory setting
- [ms]
Data type: Unsigned16
Data set: -
Factory setting
0
1-279