PcCtrl active
r0807.0
[2501.2]
Setpoint from external OP or operating tool
Main setpoint
p1070 [C]
<4>
(755[0])
Main setp scal
p1071 [C]
Suppl setp scal
p1076 [C]
Suppl setpoint
p1075 [C]
<4>
(0)
<1> Jogging can only be activated in the operating state “Ready for operation (S2)“.
<2> If technology controller is activated (p2200 > 0, p2251 = 0) connected with r2349.4.
<3> If technology controller is activated (p2200 > 0, p2251 = 0) connected with r2294.
<4> The connection to the source for the main and additional setpoint is estabished automatically via the setting in p1000.
1
2
Setpoint channel
Main/supplementary setpoint, setpoint scaling, jogging
Main setpoint eff [1/min]
r1073
+
0
+
1
Total setp
p1109 [C]
(0)
<3>
(1)
Total setp sel
p1108 [C]
<2>
(0)
(1)
3
4
<1>
STW seq_ctrl
p1055
r0898
r0898
.8
[2501.7]
STW seq_ctrl
p1056
r0898
r0898
.9
[2501.7]
Total setpoint eff [1/min]
r1078
1
0
Jog 1 n_set
-210000.000 ... 210000.000 [1/min]
p1058 [D] (150.000)
Jog 2 n_set
-210000.000 ... 210000.000 [1/min]
p1059 [D] (-150.000)
Keep old setpoint
5
6
Function diagram
FP_3030_97_51.vsd
G120 CU240B/E-2
13.12.2010
V4.4
0 0
0 1
n_set_1
[3040.1]
1 0
1 1
Suppl setpoint eff [1/min]
r1077
7
8
- 3030 -