r2349.0...12
CO/BO: Technology controller status word / Tec_ctrl status
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the status word of the technology controller.
Bit field:
Bit
Signal name
00
Technology controller de-activated
01
Technology controller limited
02
Technology controller, motorized potentiom-
eter limited max.
03
Technology controller, motorized potentiom-
eter limited min.
04
Technology controller speed setpoint total in
setpoint channel
05
Technology controller RFG bypassed in the
setpoint channel
06
Technology controller starting value at the
current limit
08
Technology controller actual value at the
minimum
09
Technology controller actual value at the
maximum
10
Technology controller output at the mini-
mum
11
Technology controller output at the maxi-
mum
12
Fault response active
p2900[0...n]
CO: Fixed value 1 [%] / Fixed value 1 [%]
Access level: 3
Can be changed: U, T
Units group: -
Min
-10000.00 [%]
Description:
Sets a fixed percentage.
Dependency:
Refer to: p2901, p2930
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
The value can be used to interconnect a scaling function (e.g. scaling of the main setpoint)
p2901[0...n]
CO: Fixed value 2 [%] / Fixed value 2 [%]
Access level: 3
Can be changed: U, T
Units group: -
Min
-10000.00 [%]
Description:
Sets a fixed percentage.
Dependency:
Refer to: p2900, p2930
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
The value can be used to interconnect a scaling function (e.g. scaling of the supplementary setpoint)
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
10000.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
10000.00 [%]
Parameters
List of Parameters
Data type: Unsigned32
Data set: -
Factory setting
-
0 signal
No
No
No
No
No
No
Yes
No
No
No
No
No
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.00 [%]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.00 [%]
FP
-
-
-
-
-
-
-
-
-
-
-
-
1-315