Siemens CU240B-2 Parameter Manual page 679

Table of Contents

Advertisement

C01700
SI Motion P1: STOP A initiated
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive is stopped via a STOP A (pulses are suppressed via the safety shutdown path of processor 1).
Possible causes:
- stop request from processor 2.
- Pulses not suppressed after test stop selection.
- subsequent response to the message C01706 "SI Motion P1: SAM/SBR limit exceeded".
- Subsequent response to the message C01714 "SI Motion P1: Safely-Limited Speed exceeded".
- Subsequent response to the message C01701 "SI Motion P1: STOP B initiated".
Remedy:
- remove the cause of the fault on the monitoring channel of processor 2.
- carry out a diagnostics routine for message C01706.
- carry out a diagnostics routine for message C01714.
- carry out a diagnostics routine for message C01701.
- check the shutdown path of processor 1.
- replace Power Module.
- replace Control Unit.
This message can be acknowledged without a POWER ON as follows:
- via F-DI or PROFIsafe.
Note:
F-DI: Failsafe Digital Input
SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SBR: Safe Brake Ramp (safe brake ramp monitoring)
C01701
SI Motion P1: STOP B initiated
Reaction:
OFF3
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive is stopped via a STOP B (braking along the OFF3 deceleration ramp).
As a result of this fault, after the speed threshold parameterized in p9560 is fallen below, message C01700 "STOP
A initiated" is output.
Possible causes:
- stop request from processor 2.
- Subsequent response to the message C01714 "SI Motion P1: Safely-Limited Speed exceeded".
- subsequent response to the message C01711 "SI Motion P1: Defect in a monitoring channel".
- subsequent response to the message C01707 "SI Motion P1: tolerance for safe operating stop exceeded".
Remedy:
- remove the cause of the fault on the monitoring channel of processor 2.
- carry out a diagnostics routine for message C01714.
- carry out a diagnostics routine for message C01711.
- carry out a diagnostics routine for message C01707.
This message can be acknowledged without a POWER ON as follows:
- motion monitoring functions integrated in the drive: F-DI or PROFIsafe.
Note:
F-DI: Failsafe Digital Input
C01706
SI Motion P1: SAM/SBR limit exceeded
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
Motion monitoring functions with set acceleration monitoring (p9506 = 3):
SAM - safe acceleration monitoring. After initiating STOP B (SS1) the velocity has exceeded the selected tolerance.
Motion monitoring functions with set brake ramp monitoring (p9506 = 1):
SBR - Safe brake ramp monitoring. After initiating STOP B (SS1) or SLS changeover to the lower speed stage, the
speed has exceeded the selected tolerance.
The drive is shut down by the message C01700 "SI Motion: STOP A initiated".
Remedy:
Check the braking behavior and, if necessary, adapt the tolerance for the parameter settings of the "SAM" or the
"SBR" function.
This message can be acknowledged without a POWER ON as follows:
- motion monitoring functions integrated in the drive: via F-DI or PROFIsafe.
Note:
F-DI: Failsafe Digital Input
SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SBR: Safe Brake Ramp (safe brake ramp monitoring)
See also: p9548 (SI Motion SAM actual velocity tolerance (Control Unit)), p9581 (SI Motion brake ramp reference
value (processor 1)), p9582 (SI Motion brake ramp delay time (processor 1)), p9583 (SI Motion brake ramp
monitoring time (processor 1))
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Faults and Alarms
List of Faults and Alarms
3-679