p0300[0...n]
Motor type selection / Mot type sel
Access level: 2
Can be changed: C(1, 3)
Units group: -
Min
0
Description:
Selecting the motor type.
The first digit of the parameter value always defines the general motor type and corresponds to the third-party
motor belonging to a motor list:
1 = Rotating induction motor
2 = Rotating synchronous motor
The type information must be entered to filter motor-specific parameters and to optimize the operating characteris-
tics and behavior. For example, for synchronous motors, power factor (p0308) is neither used nor displayed (in the
BOP/IOP).
Value:
0:
1:
2:
17:
204:
Dependency:
When selecting a motor type from the 1LA7 series, parameters p0335, p0626, p0627, and p0628 of the thermal
motor model are pre-assigned as a function of p0307 and p0311.
Note:
Once the Control Unit has been powered up for the first time or if the factory settings have been defined accord-
ingly, the motor type is pre-configured to induction motor (p0300 = 1).
If a motor type has not been selected (p0300 = 0), then the drive commissioning routine cannot be exited.
p0301[0...n]
Motor code number selection / Mot code No. sel
Access level: 2
Can be changed: C(1, 3)
Units group: -
Min
0
Description:
The parameter is used to select a motor from a motor parameter list.
When changing the code number (with the exception to the value 0), all of the motor parameters are pre-assigned
from the internally available parameter lists.
Dependency:
Code numbers can only be selected for motor types that correspond to the motor type selected in p0300.
Refer to: p0300
Note:
The motor code number can only be changed if the matching catalog motor was first selected in p0300.
When selecting a catalog motor (p0300 >= 100), drive commissioning can only be exited if a code number is
selected.
p0304[0...n]
Rated motor voltage / Mot U_rated
Access level: 1
Can be changed: C(1, 3)
Units group: -
Min
0 [Vrms]
Description:
Sets the rated motor voltage (rating plate).
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note:
When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
Once the Control Unit has booted for the first time or if the factory settings have been restored, the parameter is
pre-assigned to match the power unit.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
No motor
Induction motor (rotating)
Synchronous motor (rotating, permanent-magnet)
1LA7 standard induction motor
1LE4 synchronous motor
Calculated: -
Scaling: -
Unit selection: -
Max
204
Calculated: -
Scaling: -
Unit selection: -
Max
65535
Calculated: -
Scaling: -
Unit selection: -
Max
20000 [Vrms]
Parameters
List of Parameters
Data type: Integer16
Data set: MDS
Factory setting
0
Data type: Unsigned16
Data set: MDS
Factory setting
0
Data type: FloatingPoint32
Data set: MDS
Factory setting
0 [Vrms]
1-53

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents