Faults and Alarms
List of Faults and Alarms
A30042
Power unit: Fan operating time reached or exceeded
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum operating time of the fan in the power unit is set in p0252.
This message indicates the following:
Fault value (r0949, decimal interpretation):
0: The maximum fan operating time is 500 hours.
1: The maximum fan operating time has been exceeded.
Remedy:
Replace the fan in the power unit and reset the operating hours counter to 0 (p0251 = 0).
A30049
Power unit: Internal fan faulty
Reaction:
NONE
Acknowledge:
NONE
Cause:
The internal fan has failed.
Remedy:
Check the internal fan and replace if necessary.
F30052
EEPROM data error
Reaction:
NONE
Acknowledge:
POWER ON
Cause:
EEPROM data error of the power unit module.
Fault value (r0949, interpret hexadecimal):
0: The EEPROM data read in from the power unit module is inconsistent.
1: The EEPROM data is not compatible with the CU firmware.
Remedy:
For fault value = 0:
Replace power unit module.
For fault value = 1:
Replace power unit module.
A30054 (F)
Power unit: Undervoltage when opening the brake
Reaction:
NONE
Acknowledge:
NONE
Cause:
When the brake is being opened, it is detected that the power supply voltage is less than 24 V - 10% = 21.6V.
Alarm value (r2124, interpret decimal):
Supply voltage fault [0.1 V].
Example:
Alarm value = 212 --> voltage = 21.2 V
Remedy:
Check the 24V power supply for stability and value.
F30055
Power unit: Braking chopper overcurrent
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
An overcurrent condition has occurred in the braking chopper.
Remedy:
- check whether the braking resistor has a short circuit.
- for an external braking resistor, check whether the resistor may have been dimensioned too small.
Note:
The braking chopper is only enabled again at pulse enable after the fault has been acknowledged.
F30059
Power unit: Internal fan faulty
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The internal power unit fan has failed and is possibly defective.
Remedy:
Check the internal fan and replace if necessary.
3-718
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011