p1038[0...n]
Motorized potentiometer minimum speed / MotP n_min
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
-210000.000 [rpm]
Description:
Sets the minimum speed/velocity for the motorized potentiometer.
Note:
This parameter is automatically pre-assigned in the commissioning phase.
The setpoint output from the motorized potentiometer is limited to this value (see function diagram 3020).
p1039[0...n]
BI: Motorized potentiometer inversion / MotP inv
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to invert the minimum speed/velocity or the maximum speed/velocity for the motorized
potentiometer.
Dependency:
Refer to: p1037, p1038
Note:
The inversion is only active during "motorized potentiometer raise" or "motorized potentiometer lower".
p1040[0...n]
Motorized potentiometer starting value / Mop start value
Access level: 2
Can be changed: U, T
Units group: 3_1
Min
-210000.000 [rpm]
Description:
Sets the starting value for the motorized potentiometer. This starting value becomes effective after the drive has
been powered up.
Dependency:
Only effective if p1030.0 = 0.
Refer to: p1030
p1041[0...n]
BI: Motorized potentiometer manual/automatic / Mop manual/auto
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to change over from manual to automatic when using a motorized potentiometer.
In the manual mode, the setpoint is changed using two signals - raise and lower. In the automatic mode, the set-
point must be interconnected via a connector input.
Dependency:
Refer to: p1030, p1035, p1036, p1042
Note:
The effectiveness of the internal ramp-function generator can be set in automatic mode.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
210000.000 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: p0505
Max
210000.000 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.000 [rpm]
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.000 [rpm]
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
1-141