p0628[0...n]
Motor overtemperature rotor winding / Mot T_over rotor
Access level: 4
Can be changed: C(3), U, T
Units group: 21_2
Min
20 [K]
Description:
Defines the rated overtemperature of the squirrel cage rotor referred to ambient temperature.
Dependency:
For 1LA7 motors (refer to p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Note:
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
r0630[0...n]
Motor temperature model ambient temperature / MotTMod T_amb.
Access level: 4
Can be changed: -
Units group: 21_1
Min
- [°C]
Description:
Displays the ambient temperature of the motor temperature model.
r0631[0...n]
Motor temperature model, stator core temperature / MotTMod T_core
Access level: 4
Can be changed: -
Units group: 21_1
Min
- [°C]
Description:
Displays the stator core temperature of the motor temperature model.
r0632[0...n]
Motor temperature model, stator winding temperature / MotTMod T_copper
Access level: 4
Can be changed: -
Units group: 21_1
Min
- [°C]
Description:
Displays the stator winding temperature of the motor temperature model.
r0633[0...n]
Motor temperature model, rotor temperature / MotTMod T_rotor
Access level: 4
Can be changed: -
Units group: 21_1
Min
- [°C]
Description:
Displays the rotor temperature of the motor temperature model.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Calculated: -
Scaling: -
Unit selection: p0505
Max
200 [K]
Calculated: -
Scaling: p2006
Unit selection: p0505
Max
- [°C]
Calculated: -
Scaling: p2006
Unit selection: p0505
Max
- [°C]
Calculated: -
Scaling: p2006
Unit selection: p0505
Max
- [°C]
Calculated: -
Scaling: p2006
Unit selection: p0505
Max
- [°C]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: MDS
Factory setting
100 [K]
Data type: FloatingPoint32
Data set: MDS
Factory setting
- [°C]
Data type: FloatingPoint32
Data set: MDS
Factory setting
- [°C]
Data type: FloatingPoint32
Data set: MDS
Factory setting
- [°C]
Data type: FloatingPoint32
Data set: MDS
Factory setting
- [°C]
1-85