Siemens CU240B-2 Parameter Manual page 19

Table of Contents

Advertisement

p0010
Drive commissioning parameter filter / Drv comm. par_filt
PM240
Access level: 1
PM250
Can be changed: C(1), T
PM260
Units group: -
CU240E-2
CU240E-2 DP
CU240E-2 DP F
CU240E-2 F
Min
0
Description:
Sets the parameter filter to commission a drive.
Setting this parameter filters out the parameters that can be written into in the various commissioning steps.
Value:
0:
1:
2:
3:
5:
15:
29:
30:
39:
49:
95:
Dependency:
Refer to: r3996
Notice:
When the parameter is reset to a value of 0, short-term communication interruptions may occur.
Note:
The drive can only be powered up outside the drive commissioning (inverter enable). To realize this, this parameter
must be set to 0.
By setting p3900 to a value other than 0, the quick commissioning is completed, and this parameter is automatically
reset to 0.
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Once the Control Unit has been booted up for the first time, the motor parameters suitable for the power unit have
been defined, and the control parameters have been calculated accordingly, p0010 is automatically reset to 0.
p0010 = 3 is used for the subsequent commissioning of additional drive data sets (creating data sets: see p0010 =
15).
p0010 = 29, 39, 49: Only for internal Siemens use!
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Ready
Quick commissioning
Power unit commissioning
Motor commissioning
Technological application/units
Data sets
Only Siemens internal
Parameter reset
Only Siemens internal
Only Siemens internal
Safety Integrated commissioning
Calculated: -
Scaling: -
Unit selection: -
Max
95
Parameters
List of Parameters
Data type: Integer16
Data set: -
Factory setting
1
1-19