Siemens CU240B-2 Parameter Manual page 252

Table of Contents

Advertisement

Parameters
List of Parameters
r2004
Reference power / P_ref
Access level: 3
Can be changed: -
Units group: 14_10
Min
- [kW]
Description:
Displays the reference quantity for power.
All power ratings specified as relative value are referred to this reference quantity.
The reference quantity in this parameter corresponds to 100% or 4000 hex or 4000 0000 hex.
Dependency:
This value is calculated as follows:
Infeed: Calculated from voltage times current.
Closed-loop control: Calculated from torque times speed.
Refer to: p2000, p2001, p2002, p2003
Note:
If a BICO interconnection is established between different physical quantities, then the particular reference quanti-
ties are used as internal conversion factor.
The reference power is calculated as follows:
- 2 * Pi * reference speed / 60 * reference torque (motor)
- reference voltage * reference current * root(3) (infeed)
p2005
Reference angle / Reference angle
Access level: 4
Can be changed: T
Units group: -
Min
90.00 [°]
Description:
Sets the reference quantity for angle.
All angles specified as relative value are referred to this reference quantity.
The reference quantity in this parameter corresponds to 100% or 4000 hex or 4000 0000 hex.
Dependency:
This parameter is only updated during the automatic calculation (p0340 = 1, p3900 > 0) if motor commissioning was
carried out beforehand for drive data set zero. This means that the parameter is not locked against overwriting
using p0573 = 1.
Note:
If a BICO interconnection is established between different physical quantities, then the particular reference quanti-
ties are used as internal conversion factor.
p2006
Reference temp / Ref temp
Access level: 3
Can be changed: T
Units group: -
Min
50.00 [°C]
Description:
Sets the reference quantity for temperature.
All temperatures specified as relative value are referred to this reference quantity.
The reference quantity in this parameter corresponds to 100% or 4000 hex or 4000 0000 hex.
1-252
Calculated: -
Scaling: -
Unit selection: p0505
Max
- [kW]
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
180.00 [°]
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
300.00 [°C]
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: FloatingPoint32
Data set: -
Factory setting
- [kW]
Data type: FloatingPoint32
Data set: -
Factory setting
90.00 [°]
Data type: FloatingPoint32
Data set: -
Factory setting
100.00 [°C]
© Siemens AG 2011 All Rights Reserved