Parameters
List of Parameters
p2235[0...n]
BI: Technology controller motorized potentiometer raise setpoint / Tec_ctrl mop raise
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to continually increase the setpoint for the motorized potentiometer of the technology control-
ler.
The setpoint change (CO: r2250) depends on the set ramp-up time (p2247) and the duration of the signal that is
present (BI: p2235).
Dependency:
Refer to: p2236
p2236[0...n]
BI: Technology controller motorized potentiometer lower setpoint /
Tec_ctrl mop lower
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to continually reduce the setpoint for the motorized potentiometer of the technology control-
ler.
The setpoint change (CO: r2250) depends on the set ramp-down time (p2248) and the duration of the signal that is
present (BI: p2236).
Dependency:
Refer to: p2235
p2237[0...n]
Technology controller motorized potentiometer maximum value / Tec_ctrl mop max
Access level: 3
Can be changed: U, T
Units group: 9_1
Min
-200.00 [%]
Description:
Sets the maximum value for the motorized potentiometer of the technology controller.
Dependency:
Refer to: p2238
p2238[0...n]
Technology controller motorized potentiometer minimum value / Tec_ctrl mop min
Access level: 2
Can be changed: U, T
Units group: 9_1
Min
-200.00 [%]
Description:
Sets the minimum value for the motorized potentiometer of the technology controller.
Dependency:
Refer to: p2237
p2240[0...n]
Technology controller motorized potentiometer starting value / Tec_ctrl mop start
Access level: 2
Can be changed: U, T
Units group: 9_1
Min
-200.00 [%]
Description:
Sets the starting value for the motorized potentiometer of the technology controller.
For p2230.0 = 0, this setpoint is entered after ON.
Dependency:
Refer to: p2230
1-304
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: p0595
Max
200.00 [%]
Calculated: -
Scaling: -
Unit selection: p0595
Max
200.00 [%]
Calculated: -
Scaling: -
Unit selection: p0595
Max
200.00 [%]
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
0
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
100.00 [%]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
-100.00 [%]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.00 [%]
© Siemens AG 2011 All Rights Reserved