Siemens CU240B-2 Parameter Manual page 312

Table of Contents

Advertisement

Parameters
List of Parameters
r2294
CO: Technology controller output signal / Tec_ctrl outp_sig
Access level: 2
Can be changed: -
Units group: -
Min
- [%]
Description:
Displays the output signal of the technology controller.
Dependency:
Refer to: p2295
p2295
CO: Technology controller output scaling / Tec_ctrl outp scal
Access level: 3
Can be changed: U, T
Units group: -
Min
-100.00 [%]
Description:
Sets the scaling for the output signal of the technology controller.
p2296[0...n]
CI: Technology controller output scaling / Tec_ctrl outp scal
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for the scaling value of the technology controller.
Dependency:
Refer to: p2295
p2297[0...n]
CI: Technology controller maximum limit signal source / Tec_ctrl m_lm s_sc
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for the maximum limiting of the technology controller.
Dependency:
Refer to: p2291
Note:
In order that the output of the technology controller does not exceed the maximum speed limit, its upper limit p2297
should be connected to the actual maximum speed r1084.
In mode p2251 = 1, p2299 must also be connected to the output of the ramp-function generator r1150.
p2298[0...n]
CI: Technology controller minimum limit signal source / Tec_ctrl min_l s_s
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for the minimum limiting of the technology controller.
Dependency:
Refer to: p2292
Note:
If the technology controller is rotated in a negative direction in mode p2251 = 0, its lower limit p2298 should be con-
nected to the actual minimum speed r1087.
In mode p2251 = 1, p2299 must also be connected to the output of the ramp-function generator r1150.
1-312
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
- [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
100.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: FloatingPoint32
Data set: -
Factory setting
- [%]
Data type: FloatingPoint32
Data set: -
Factory setting
100.00 [%]
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
2295[0]
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
1084[0]
Data type: U32 / FloatingPoint32
Data set: CDS, p0170
Factory setting
1087[0]