Siemens CU240B-2 Parameter Manual page 24

Table of Contents

Advertisement

Parameters
List of Parameters
r0030
Current actual value torque-generating smoothed / Iq_act smooth
Access level: 4
Can be changed: -
Units group: -
Min
- [Arms]
Description:
Displays the smoothed torque-generating actual current.
Dependency:
Refer to: r0078
Note:
Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The torque-generating current actual value is available smoothed (r0030) and unsmoothed (r0078).
r0031
Actual torque smoothed / M_act smooth
Access level: 2
Can be changed: -
Units group: 7_1
Min
- [Nm]
Description:
Displays the smoothed torque actual value.
Dependency:
Refer to: r0080
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The active current actual value is available smoothed (r0031) and unsmoothed (r0080).
r0032
CO: Active power actual value smoothed / P_actv_act smth
Access level: 2
Can be changed: -
Units group: 14_10
Min
- [kW]
Description:
Displays the smoothed actual value of the active power.
Dependency:
Refer to: r0082
Notice:
This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
Note:
Power delivered at the motor shaft.
The active power is available smoothed (r0032 with 100 ms) and unsmoothed (r0082).
1-24
Calculated: -
Scaling: p2002
Unit selection: -
Max
- [Arms]
Calculated: -
Scaling: p2003
Unit selection: p0505
Max
- [Nm]
Calculated: -
Scaling: r2004
Unit selection: p0505
Max
- [kW]
SINAMICS G120 / Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
Data type: FloatingPoint32
Data set: -
Factory setting
- [Arms]
Data type: FloatingPoint32
Data set: -
Factory setting
- [Nm]
Data type: FloatingPoint32
Data set: -
Factory setting
- [kW]
© Siemens AG 2011 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f

Table of Contents