Siemens CU240B-2 Parameter Manual page 257

Table of Contents

Advertisement

p2030
Field bus int protocol selection / Field bus protocol
CU240B-2 DP
Access level: 1
CU240E-2 DP
Can be changed: T
CU240E-2 DP F
Units group: -
Min
0
Description:
Sets the communication protocol for the field bus interface.
Value:
0:
3:
Notice:
For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note:
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
r2032
Master control, control word effective / PcCtrl STW eff
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the effective control word 1 (STW1) of the drive for the master control.
Bit field:
Bit
Signal name
00
ON/OFF1
01
OC / OFF2
02
OC / OFF3
03
Operation enable
04
Ramp-function generator enable
05
Start ramp-function generator
06
Speed setpoint enable
07
Acknowledge fault
08
Jog bit 0
09
Jog bit 1
10
Master ctrl by PLC
Notice:
The master control only influences control word 1 and speed setpoint 1. Other control words/setpoints can be trans-
ferred from another automation device.
Note:
OC: Operating condition
p2037
PROFIdrive STW1.10 = 0 mode / PD STW1.10=0
CU240B-2 DP
Access level: 3
CU240E-2 DP
Can be changed: T
CU240E-2 DP F
Units group: -
Min
0
Description:
Sets the processing mode for PROFIdrive STW1.10 "master control by PLC".
Generally, control world 1 is received with the first receive word (PZD1) (this is in conformance to the PROFIdrive
profile). The behavior of STW1.10 = 0 corresponds to that of the PROFIdrive profile. For other applications that
deviate from this, the behavior can be adapted using this particular parameter.
Value:
0:
1:
2:
Note:
If the STW1 is not transferred according to the PROFIdrive with PZD1 (with bit 10 "master control by PLC"), then
p2037 should be set to 2.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU240B/E-2 Parameter Manual (LH11), 01/2011
No protocol
PROFIBUS
Freeze setpoints and continue to process sign-of-life
Freeze setpoints and sign-of-life
Setpoints are not frozen
Calculated: -
Scaling: -
Unit selection: -
Max
3
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
2
Parameters
List of Parameters
Data type: Integer16
Data set: -
Factory setting
3
Data type: Unsigned16
Data set: -
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
No
Data type: Integer16
Data set: -
Factory setting
0
FP
-
-
-
-
-
-
-
-
3030
3030
-
1-257

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120Cu240e-2Cu240b-2 dpCu240e-2 dpCu240e-2 fCu240e-2 dp f