Tunstall FlamencoIP+ Manual page 419

Table of Contents

Advertisement

DE - Anschlüsse
Power supply unit 5A, DIN rail (77 3410 50)
+ UPS control unit 10A (77 3411 00)
+ Ba ery module (77 3412 00)
Connec on for poten al equalisa on
on the threaded bolt in the housing:
Internal poten al
equalisa on connec on
Important notes
Check all cables for con nuity, short circuits and ground
faults.
When the data cables are correctly connected, the values
are: voltage between DH and DG and voltage between
DL and DG approx. 2.5 V.
ATTENTION! The connec on plan on the following page is
a standard connec on plan. Please follow the devia ons
in your project specific connec on plan.
00 8802 52, 03/21 (Rev. 4.0)
DANGER! Poten al equalisa on required.
Ferrite
(order no. 00 0080 34)
Fault message output
Poten al-free output.
Collec ve output.
Contact load: max. 100 mA / 24 V.
In case of a fault contact opens at the screw clamps.
Fault message output switches in case of:
Disconnected or defec ve OSYnet bus user.
Disconnected or defec ve RAN bus user.
Interrupted power supply on the ward.
Interrupted power supply at the OSY-ControlCenter.
Interrupted OSYnet bus line.
OSY-ControlCenter does not boot-up.
Assignment for the 9 pole Sub-D connector:
RxD = 2
TxD = 3
GND= 5
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7
Group 8
Don't connect, if telephone line 5, 6, 7 or 8 is used.
Don't connect, if telephone line 1, 2, 3 or 4 is used.
Verpackungsbeilagen 03/22, Seite 168
EN - Connections
2 x 2.5 mm²
10 cm
Data Group 1
Data Group 2
Data Group 3
Data Group 4
Data Group 5
Data Group 6
Data Group 7
Data Group 8
Speech Group 1
Speech Group 2
Speech Group 3
Speech Group 4
Speech Group 5
Speech Group 6
Speech Group 7
Speech Group 8
Otherwise use for: Speech Group 17 - 20.
Otherwise use for: Speech Group 21 - 24.
Telephone Line 1
Telephone Line 2
Telephone Line 3
Telephone Line 4
Telephone Line 5
Telephone Line 6
Telephone Line 7
Telephone Line 8
- 4 -
Pre-connected
Network switch
pre-connected