8.2

IO Test

8.2.1

Data Dialog

The WAGO-I/O-CHECK commissioning tool makes it possible to display and
specify the process data of the I/O module. This means that the field wiring can
be checked during commissioning without the node having to be connected to a
fieldbus system.
Open the data dialog either by double-clicking the I/O module in the node view or
via the context menu of the selected I/O module (menu item "Process data ...").
The data dialog is divided into individual areas (for each channel or channel
group):
Figure 28: Data Dialog (Sample Excerpt)

Table 58: Data Dialog Legend

Item
Explanation
1
The data dialog groups an area with information and setting options for
each channel (or, if applicable, channel group).
2
The current settings are displayed on the left.
No changes can be made.
3
The process data of the channel is displayed on the right.
You have the option of changing the output data.
4
The lower setting range applies to 2 channels each. You can specify
whether you want to enable the channels by double-clicking the
corresponding checkbox:
If the checkbox is empty, the outputs of the I/O module are high-
impedance (Tri-State).
If the checkmark is set in the respective checkbox, the outputs
are enabled and are then no longer high-impedance.
Commissioning
81
Manual
Version 1.0.0