PROCEDURES BEFORE OPERATION
This chapter describes the procedures before operation.
1.
Setting the IP address/station number setting switches
Set the fourth octet of IP address of I/O module.
Page 118 Setting the IP address/station number setting switches
2.
Function setting switch setting
Set functions of the I/O module.
In the factory default switch status, the I/O module operates in the following settings. Change the switch status as necessary.
• Input response time setting: 1ms (I/O module (except for waterproof module)), 10ms (I/O module (waterproof module))
• Output HOLD/CLEAR setting: CLEAR
• Communication speed setting: 1Gbps
• CC-Link IE TSN Network synchronous communication setting: Synchronous X/Y control mode
Page 120 Function setting switch setting
3.
Connection
Mount the I/O modules (except for waterproof modules) on a DIN rail. Or fix the I/O modules (waterproof modules).
Page 125 Mounting the I/O modules (except for waterproof module) on a DIN rail
Page 126 Fixing the I/O module (waterproof module)
4.
Wiring
Wire the power supply, Ethernet cables, and external devices to the I/O modules.
Page 127 Wiring of Terminal Block for Module Power Supply and FG
Page 132 Wiring the I/O Module (Waterproof Module) to the Power Supply
Page 133 Wiring of Ethernet Cable
Page 136 Wiring of I/O Module and External Device
5.
Parameter setting
Set the network parameters.
Page 151 Network Configuration Setting
6.
Programming
Create a program.
To replace the I/O module, follow the procedure described below:
• Power off the I/O module and remove it.
• Prepare a new I/O module and perform the procedure from step 1 to step 4. At this time, the settings of the
IP address/station number setting switches and function setting switch must be the same as the settings for
I/O module before replacement.
• Check that the RUN LED and DATA LINK LED of I/O module are on and the ERR. LED is off before
restarting control operation.