NZ2GN12A2-16T transistor output module
Item
Station type
Authentication Class
Network topology
Number of output points
Rated load voltage
Max. load current
Maximum inrush current
Leakage current at OFF
Max. voltage drop at ON
Output response time
Surge suppressor
External power supply for
*3
output part
Withstand voltage
Insulation resistance
Noise immunity
Protection degree
Wiring method for common
Protection function
External interface
Applicable waterproof
connector
Multicast filter
Cyclic transmission
*3
Module power supply
Weight
*1 Make sure that the total amount of output current that flows through one connector is 4A or less.
*2 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC-Link IE
TSN Configuration window. According to the function used, set an appropriate number of points. ( Page 226 Output module (16-
point module))
*3 For a power supply to be connected to the waterproof I/O module (such as the module-and-sensor power supply or the load power
supply and external power supply for output part), use the power supply that meets the following condition.
SELV (Safety Extra Low Voltage): Product with reinforced insulation from the hazardous potential part (60V or higher)
3 SPECIFICATIONS
62
3.3 Performance Specifications
NZ2GN12A2-16T
Remote station
Authentication Class B
Line topology, star topology, mixture of star topology and line topology, ring topology
16 points
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
4A/point (Y0 to Y3)
Current is limited by the overload protection function.
0.1mA or less
0.25VDC (TYP.) 2A, 0.5VDC (MAX.) 2A, 0.5VDC (TYP.) 4A, 0.1VDC (MAX.) 4A
OFF  ON
0.5ms or less
ON  OFF
0.8ms or less (resistive load)
Zener diode
Voltage
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
Current
25mA or less (TYP. 24VDC per common) External load current is not included.
720VDC for 1 minute between all DC external terminals and ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP67
16 points/common (2-wire, waterproof connector type)
Sink type
Overload protection
Limited current when detecting overcurrent: 9A or more/point
function
Activated to each point.
Overheat protection
Activated to each point.
function
Communication part
M12 waterproof connector, 8 pins, female, X-code
Module power supply part
M12 waterproof connector, 5 pins, male, female, L-code
I/O part
M12 waterproof connector, 5 pins, female, A-code
Page 148 List of Recommended Cables/Connectors for the I/O Module (Waterproof Module)
For communications
For power supply
For I/O
Y-branch connector for I/O
Available
RX/RY points
16 points
RWr/RWw points
4 points
Voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current
110mA or less (24VDC, all points ON)
0.42kg
*1
, 2A/point (Y4 to YF), 12A/common