Mitsubishi Electric NZ2GN2S1-16D User Manual page 19

Programmable controller; cc-link ie tsn remote i/o module; cc-link ie tsn communication mode
Hide thumbs Also See for NZ2GN2S1-16D:
Table of Contents

Advertisement

• Waterproof/dustproof connector type
(13)
(6)
(12)
(1)
(4)
(5)
(3)
(2)
(10)
(11)
(14)
No.
Name
(1)
PW LED
RUN LED
ERR. LED
P1 LINK LED
P2 LINK LED
DATA LINK LED
(2)
IP address/station number
setting switch
(3)
Function setting switch
■16-point module
(4)
X0 LED to XF LED
■32-point module
X0 LED to X1F LED
■16-point module
Y0 LED to YF LED
■32-point module
Y0 LED to Y1F LED
(5)
I/O PW LED
Application
Indicates the power supply status of the I/O module.
On: Power supply ON
Off: Power supply OFF
Indicates the operating status of the I/O module.
On: Operating normally.
Flashing: Operating in unit test mode
Off: A major error has occurred.
Indicates the error status of the I/O module.
On: A moderate error or major error has occurred.
Flashing: A minor error has occurred.
Off: Operating normally.
Indicates the link status for P1.
On: Link-up
Off: Linkdown in progress
Indicates the link status for P2.
On: Link-up
Off: Linkdown in progress
Indicates the data link status of the I/O module.
On: Cyclic transmission being performed
Flashing: Cyclic transmission stopped
Off: Disconnected
Sets the fourth octet of the IP address.
Page 118 Setting the IP address/station number setting switches
Sets functions of the I/O module.
Page 120 Function setting switch setting
Indicates the ON/OFF status of the inputs.
On: Input ON
Off: Input OFF
Indicates the ON/OFF status of the outputs.
On: Output ON
Off: Output OFF
Indicates the status of the power supply from the external power supply.
On: External power supply ON
Off: External power supply OFF
*1
*2
2
2 PART NAMES
17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents