Module operation area
■Device number
Name
Module operation area
■Description
This area is intended for module operation.
RWw0
b0 to b9
b10
b11 to b15
■Error clear request flag (RWw0.b10)
Turning on Error clear request flag (RWw0.b10) after eliminating the cause of the error changes the error code (RWr1) to 0.
Some error cannot be cleared with Error clear request flag (RWw0.b10) depending on its details.
• Operation in the event of a minor error
CPU minor error status of
each station (1)
OFF
Error code
0000H
(RWr1)
Error clear request flag
OFF
(RWw0.b10)
I/O control status
Performed by I/O module
Executed by the program
(1) Use the bit for the target station in SW0110 to SW0117 (individual station CPU minor error status) of the master station.
• Operation in the event of a moderate error
CPU moderate/major error
status of each station (1)
OFF
Error code
0000H
(RWr1)
Error clear request flag
OFF
(RWw0.b10)
Control
I/O control status
performed
Performed by I/O module
Executed by the program
(1) Use the bit for the target station in SW0100 to SW0107 (individual station CPU moderate error status) of the master station.
Device number
RWw0
Name
Use prohibited
Error clear request flag
Use prohibited
ON
(Error code)
ON
Control performed
ON
(Error code)
ON
Control stopped
OFF
0000H
OFF
OFF
0000H
OFF
Control performed
Appendix 2 Remote Register