Mitsubishi Electric NZ2GN2S1-16D User Manual page 239

Programmable controller; cc-link ie tsn remote i/o module; cc-link ie tsn communication mode
Hide thumbs Also See for NZ2GN2S1-16D:
Table of Contents

Advertisement

Output Y OFF information
■Device number
Name
Output Y OFF information
■Description
Whether output Y has been turned off or not can be checked with Output Y OFF information Y (RWrE, RWrF).
When the synchronization output timing setting control or the output time setting control (CC-Link IE TSN
Network synchronous communication function) is used, whether output Y has been turned off or not can be
checked with Output Y OFF information Y (RWrE, RWrF).
■Output Y OFF information Y0 to YF (RWrE)
b15
b14
b13
b12
YF
YE
YD
YC
Off: Output Y has never been turned off.
On: Output Y has been turned off.
■Output Y OFF information Y10 to Y1F (RWrF)
b15
b14
b13
b12
Y1F
Y1E
Y1D
Y1C
Off: Output Y has never been turned off.
On: Output Y has been turned off.
Output Y OFF information Y (RWrE, RWrF) can be cleared using Output Y OFF information clear request Y (RWwE,
RWwF).
ON
Remote output signal RY0
ON
Output Y current value Y0
(RWrA. b0)
ON
External output signal Y0
Output Y OFF information Y0
OFF
(RWrE.b0)
Output Y OFF information
OFF
clear request Y0 (RWwE.b0)
Performed by I/O module
Executed by the program
(1) Remains on even after Y0 turns on.
(2) Turns off when the clear request turns on.
While Output Y OFF information clear request is turned on, regardless of the remote output signal status,
output Y OFF information continues to be cleared.
b11
b10
b9
b8
YB
YA
Y9
Y8
b11
b10
b9
b8
Y1B
Y1A
Y19
Y18
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
(1)
Device number
RWrE, RWrF
b7
b6
b5
b4
Y7
Y6
Y5
Y4
b7
b6
b5
b4
Y17
Y16
Y15
Y14
ON
b3
b2
b1
b0
Y3
Y2
Y1
Y0
b3
b2
b1
b0
Y13
Y12
Y11
Y10
(2)
OFF
OFF
APPX
Appendix 2 Remote Register
A
237

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents