Function setting switch setting

Set the following functions using the function setting switch on the front of I/O module.
• Network setting function
• Input response time setting function
• Output HOLD/CLEAR setting function
• CC-Link IE TSN Network synchronous communication function
• Communication speed setting function
The setting of function setting switch is enabled when the I/O module is powered on. Thus, set each function when the module
is powered off.
When operating the function setting switch, use a flathead screwdriver having a blade of 1.2mm or less in
width.
Setting procedure
Set each function with function setting switch 1 to function setting switch 10.
Switch name
Function setting switch 1
Function setting switch 2 to function
setting switch 4
Function setting switch 5
Function setting switch 6, function
setting switch 7
Function setting switch 8, function
setting switch 9
Function setting switch 10
Do not change any function setting switch while the I/O module is powered on. If the setting of a function
setting switch is changed while the I/O module is powered on, one of the errors from Function setting switch 1
changed error (error code: 0201H) to Function setting switch 10 changed error (error code: 020AH) occurs,
and the changed setting of that function setting switch is not applied. Returning the function setting switch to
its previous position and turning on Error clear request flag (RWw0.b10) eliminate the error.
6 INSTALLATION AND WIRING
120
6.2 Setting Switch
Function name
NETWORK
Network setting function
RESPONSE
Input response time setting
function
HOLD/CLEAR
Output HOLD/CLEAR setting
function
MODE
CC-Link IE TSN Network
synchronous communication
function
F LINK P1/P2
Use prohibited
LINK SPEED
Communication speed
setting function
Setting details
Set this switch to OFF in normal operation.
Set it to ON to perform a unit test. ( Page 198 Unit Test)
Set the input response time. ( Page 155 Setting procedure)
Set output HOLD/CLEAR. ( Page 156 Setting procedure)
■For the I/O module with the firmware version of "05" or later
Set the CC-Link IE TSN Network synchronous communication.
( Page 174 Operation mode setting)
■For the I/O module with the firmware version of "04" or earlier
Fix these switches to OFF.
Fix these switches to OFF.
■For the I/O module with the firmware version of "02" or later
Set the communication speed. ( Page 175 Setting procedure)
■For the I/O module with the firmware version of "01"
Fix this switch to OFF.