Mitsubishi Electric NZ2GN2S1-16D User Manual page 43

Programmable controller; cc-link ie tsn remote i/o module; cc-link ie tsn communication mode
Hide thumbs Also See for NZ2GN2S1-16D:
Table of Contents

Advertisement

NZ2GN12A4-16D DC input module
Item
Station type
Authentication Class
Network topology
Number of input points
Rated input voltage
Rated input current
Maximum number of simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
OFF  ON
Input response time
ON  OFF
Withstand voltage
Insulation resistance
*2
Noise immunity
Protection degree
Wiring method for common
Current supplied to external devices
External interface
Communication part
Module power supply part
I/O part
Applicable waterproof
For communications
connector
For power supply
For I/O
Y-branch connector for I/O
Multicast filter
Cyclic transmission
RX/RY points
RWr/RWw points
*4
Module power supply
Voltage
Current
Weight
*1 If the input response time is set to "0ms", the actual input response time is 80s at OFF  ON, and 160s at ON  OFF.
*2 It is the noise immunity of when the input response time setting value is other than "0ms". Note that the module is easily affected by
noise if "0ms" is set.
*3 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC-Link IE
TSN Configuration window. According to the function used, set an appropriate number of points. ( Page 224 Input module (16-point
module))
*4 For a power supply to be connected to the waterproof I/O module (such as the module-and-sensor power supply or the load power
supply and external power supply for output part), use the power supply that meets the following condition.
SELV (Safety Extra Low Voltage): Product with reinforced insulation from the hazardous potential part (60V or higher)
NZ2GN12A4-16D
Remote station
Authentication Class B
Line topology, star topology, mixture of star topology and line topology, ring topology
16 points
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
7.3mA TYP. (for 24VDC)
100%
11VDC or more/4mA or more
5VDC or less/1.5mA or less
3.0k
*1
0ms
/0.2ms/1ms/1.5ms/5ms/10ms/20ms/70ms
(Factory default: 10ms)
720VDC for 1 minute between all DC external terminals and ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP67
16 points/common (2- to 4-wire, waterproof connector type)
Positive common type
0.4A/terminal
M12 waterproof connector, 8 pins, female, X-code
M12 waterproof connector, 5 pins, male, female, L-code
M12 waterproof connector, 5 pins, female, A-code
Page 148 List of Recommended Cables/Connectors for the I/O Module (Waterproof Module)
Available
16 points
*3
4 points
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
250mA or less (24VDC, all points ON)
0.41kg
3 SPECIFICATIONS
3.3 Performance Specifications
3
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents