Mitsubishi Electric NZ2GN2S1-16D User Manual page 96

Programmable controller; cc-link ie tsn remote i/o module; cc-link ie tsn communication mode
Hide thumbs Also See for NZ2GN2S1-16D:
Table of Contents

Advertisement

Item
Weight
*1 If the input response time is set to "0ms", the actual input response time is 80s at OFF  ON, and 160s at ON  OFF.
*2 Make sure that the total amount of output current that flows through one connector is 4A or less.
*3 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC-Link IE
TSN Configuration window. According to the function used, set an appropriate number of points. ( Page 228 I/O combined module
(16-point module))
*4 For a power supply to be connected to the waterproof I/O module (such as the module-and-sensor power supply or the load power
supply and external power supply for output part), use the power supply that meets the following condition.
SELV (Safety Extra Low Voltage): Product with reinforced insulation from the hazardous potential part (60V or higher)
■Derating chart
12
8
Max. load current
(common)
(A/common)
0
0
●: Module-and-sensor power supply current, 8A
: Module-and-sensor power supply current, 6A
The module-and-sensor power supply current is 6A when the ambient temperature is 40 or higher.
3 SPECIFICATIONS
94
3.3 Performance Specifications
NZ2GN12A42-16DT
0.42kg
12A/common at 40­
40
55
Ambient temperature (­)
8A/common at 55­