Mitsubishi Electric NZ2GN2S1-16D User Manual page 79

Programmable controller; cc-link ie tsn remote i/o module; cc-link ie tsn communication mode
Hide thumbs Also See for NZ2GN2S1-16D:
Table of Contents

Advertisement

NZ2GN12A2-16TE transistor output module
Item
Station type
Authentication Class
Network topology
Number of output points
Rated load voltage
Max. load current
Maximum inrush current
Leakage current at OFF
Max. voltage drop at ON
OFF  ON
Output response time
ON  OFF
Surge suppressor
External power supply for
Voltage
*3
output part
Current
Withstand voltage
Insulation resistance
Noise immunity
Protection degree
Wiring method for common
Protection function
Overload protection
function
Overheat protection
function
External interface
Communication part
Module power supply part
I/O part
Applicable waterproof
For communications
connector
For power supply
For I/O
Y-branch connector for I/O
Multicast filter
Cyclic transmission
RX/RY points
RWr/RWw points
*3
Module power supply
Voltage
Current
Weight
*1 Make sure that the total amount of output current that flows through one connector is 4A or less.
*2 This value indicates the number of points set by default when the module is dragged and dropped to the network map in the CC-Link IE
TSN Configuration window. According to the function used, set an appropriate number of points. ( Page 226 Output module (16-
point module))
*3 For a power supply to be connected to the waterproof I/O module (such as the module-and-sensor power supply or the load power
supply and external power supply for output part), use the power supply that meets the following condition.
SELV (Safety Extra Low Voltage): Product with reinforced insulation from the hazardous potential part (60V or higher)
NZ2GN12A2-16TE
Remote station
Authentication Class B
Line topology, star topology, mixture of star topology and line topology, ring topology
16 points
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
*1
4A/point (Y0 to Y3)
, 2A/point (Y4 to YF), 12A/common
Current is limited by the overload protection function.
0.1mA or less
0.3VDC (TYP.) 2A, 0.6VDC (MAX.) 2A, 0.6VDC (TYP.) 4A, 1.2VDC (MAX.) 4A
0.5ms or less
1.0ms or less (resistive load)
Zener diode
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
45mA or less (TYP. 24VDC per common) External load current is not included.
720VDC for 1 minute between all DC external terminals and ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP67
16 points/common (2-wire, waterproof connector type)
Source type
Limited current when detecting overcurrent: 5.2A or more/point
Activated to each point.
Activated to each point.
M12 waterproof connector, 8 pins, female, X-code
M12 waterproof connector, 5 pins, male, female, L-code
M12 waterproof connector, 5 pins, female, A-code
Page 148 List of Recommended Cables/Connectors for the I/O Module (Waterproof Module)
Available
16 points
*2
4 points
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
110mA or less (24VDC, all points ON)
0.42kg
3 SPECIFICATIONS
3.3 Performance Specifications
3
77

Hide quick links:

Advertisement

Table of Contents
loading