Mitsubishi Electric NZ2GN2S1-16D User Manual page 95

Programmable controller; cc-link ie tsn remote i/o module; cc-link ie tsn communication mode
Hide thumbs Also See for NZ2GN2S1-16D:
Table of Contents

Advertisement

NZ2GN12A42-16DT DC input/transistor output module
Item
Input specifications
Number of input points
Rated input voltage
Rated input current
Maximum number of simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
OFF  ON
Input response time
ON  OFF
Wiring method for common
Current supplied to external devices
Output specifications
Number of output points
Rated load voltage
Max. load current
Maximum inrush current
Leakage current at OFF
Max. voltage drop at ON
OFF  ON
Output response time
ON  OFF
Surge suppressor
External power supply for
Voltage
*4
output part
Current
Protection function
Overload protection
function
Overheat protection
function
Wiring method for common
Common specifications
Station type
Authentication Class
Network topology
Withstand voltage
Insulation resistance
Noise immunity
Protection degree
External interface
Communication part
Module power supply part
I/O part
Applicable waterproof
For communications
connector
For power supply
For I/O
Y-branch connector for I/O
Multicast filter
Cyclic transmission
RX/RY points
RWr/RWw points
*4
Module power supply
Voltage
Current
NZ2GN12A42-16DT
8 points
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
7.3mA TYP. (for 24VDC)
100%
11VDC or more/4mA or more
5VDC or less/1.5mA or less
3.0k
*1
0ms
/0.2ms/1ms/1.5ms/5ms/10ms/20ms/70ms
(Factory default: 10ms)
8 points/common (2- to 4-wire, waterproof connector type)
Positive common type
0.4A/terminal
8 points
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
*2
4A/point (Y8 to YB)
, 2A/point (YC to YF), 12A/common
Current is limited by the overload protection function.
0.1mA or less
0.25VDC (TYP.) 2A, 0.5VDC (MAX.) 2A, 0.5VDC (TYP.) 4A, 0.1VDC (MAX.) 4A
0.5ms or less
0.8ms or less (resistive load)
Zener diode
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
20mA or less (TYP. 24VDC per common) External load current is not included.
Limited current when detecting overcurrent: 9A or more/point
Activated to each point.
Activated to each point.
8 points/common (2-wire, waterproof connector type)
Sink type
Remote station
Authentication Class B
Line topology, star topology, mixture of star topology and line topology, ring topology
720VDC for 1 minute between all DC external terminals and ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP67
M12 waterproof connector, 8 pins, female, X-code
M12 waterproof connector, 5 pins, male, female, L-code
M12 waterproof connector, 5 pins, female, A-code
Page 148 List of Recommended Cables/Connectors for the I/O Module (Waterproof Module)
Available
16 points
*3
4 points
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
160mA or less (24VDC, all points ON)
3 SPECIFICATIONS