NZ2GN12A42-16DTE DC input/transistor output module
Item
Input specifications
Number of input points
Rated input voltage
Rated input current
Maximum number of simultaneous input points
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Input response time
Wiring method for common
Current supplied to external devices
Output specifications
Number of output points
Rated load voltage
Max. load current
Maximum inrush current
Leakage current at OFF
Max. voltage drop at ON
Output response time
Surge suppressor
External power supply for
*4
output part
Protection function
Wiring method for common
Common specifications
Station type
Authentication Class
Network topology
Withstand voltage
Insulation resistance
Noise immunity
Protection degree
External interface
Applicable waterproof
connector
Multicast filter
Cyclic transmission
*4
Module power supply
3 SPECIFICATIONS
104
3.3 Performance Specifications
NZ2GN12A42-16DTE
8 points
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
7.3mA TYP. (for 24VDC)
100%
11VDC or more/4mA or more
5VDC or less/1.5mA or less
3.0k
OFF  ON
0ms
(Factory default: 10ms)
ON  OFF
8 points/common (2- to 4-wire, waterproof connector type)
Negative common type
0.4A/terminal
8 points
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
4A/point (Y8 to YB)
Current is limited by the overload protection function.
0.1mA or less
0.3VDC (TYP.) 2A, 0.6VDC (MAX.) 2A, 0.6VDC (TYP.) 4A, 1.2VDC (MAX.) 4A
OFF  ON
0.5ms or less
ON  OFF
1.0ms or less (resistive load)
Zener diode
Voltage
12/24VDC (ripple rate: 5% or less) (Allowable voltage range: 10.2 to 28.8VDC)
Current
30mA or less (TYP. 24VDC per common) External load current is not included.
Overload protection
Limited current when detecting overcurrent: 5.2A or more/point
function
Activated to each point.
Overheat protection
Activated to each point.
function
8 points/common (2-wire, waterproof connector type)
Source type
Remote station
Authentication Class B
Line topology, star topology, mixture of star topology and line topology, ring topology
720VDC for 1 minute between all DC external terminals and ground
10M or higher between all DC external terminals and ground (500VDC insulation resistance tester)
Noise voltage 500Vp-p, noise width 1s, noise frequency 25 to 60Hz (DC type noise simulator
condition)
IP67
Communication part
M12 waterproof connector, 8 pins, female, X-code
Module power supply part
M12 waterproof connector, 5 pins, male, female, L-code
I/O part
M12 waterproof connector, 5 pins, female, A-code
Page 148 List of Recommended Cables/Connectors for the I/O Module (Waterproof Module)
For communications
For power supply
For I/O
Y-branch connector for I/O
Available
RX/RY points
16 points
RWr/RWw points
4 points
Voltage
24VDC (ripple rate: 5% or less) (Allowable voltage range: 20.4 to 28.8VDC)
Current
160mA or less (24VDC, all points ON)
*1
/0.2ms/1ms/1.5ms/5ms/10ms/20ms/70ms
*2
, 2A/point (YC to YF), 12A/common
*3

Hide quick links: