Output Y ON information
■Device number
Name
Output Y ON information
■Description
Whether output Y has been turned on or not can be checked with Output Y ON information Y (RWrC, RWrD).
When the synchronization output timing setting control or the output time setting control (CC-Link IE TSN
Network synchronous communication function) is used, whether output Y has been turned on or not can be
checked with Output Y ON information Y (RWrC, RWrD).
■Output Y ON information Y0 to YF (RWrC)
b15
b14
b13
YF
YE
YD
Off: Output Y has never been turned on.
On: Output Y has been turned on.
■Output Y ON information Y10 to Y1F (RWrD)
b15
b14
b13
Y1F
Y1E
Y1D
Off: Output Y has never been turned on.
On: Output Y has been turned on.
Output Y ON information Y (RWrC, RWrD) can be cleared using Output Y ON information clear request Y (RWwC,
RWwD).
Remote output signal RY0
Output Y current value Y0
(RWrA. b0)
External output signal Y0
Output Y ON information Y0
(RWrC.b0)
Output Y ON information
clear request Y0 (RWwC.b0)
Performed by I/O module
Executed by the program
(1) Remains on even after Y0 turns off.
(2) Turns off when the clear request turns on.
While Output Y ON information clear request is turned on, regardless of the remote output signal status,
output Y ON information continues to be cleared.
APPX
236
Appendix 2 Remote Register
b12
b11
b10
b9
YC
YB
YA
Y9
b12
b11
b10
b9
Y1C
Y1B
Y1A
Y19
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
Device number
RWrC, RWrD
b8
b7
b6
Y8
Y7
Y6
b8
b7
b6
Y18
Y17
Y16
OFF
OFF
OFF
(1)
b5
b4
b3
b2
Y5
Y4
Y3
Y2
b5
b4
b3
b2
Y15
Y14
Y13
Y12
(2)
OFF
ON
OFF
b1
b0
Y1
Y0
b1
b0
Y11
Y10