■Precautions
• If a value set in ON/OFF selection flag (RWw4, RWw5) has been changed while a time earlier than the start timing of the
second synchronization cycle from the setting is set for Output time setting Y (RWw10 to RWw8F), an output change
disabled time setting error (error code: 0210H) occurs.
• The external output Y does not change while the I/O module is in the HOLD/CLEAR state, even if it is the time set in
Output time setting Y (RWw10 to RWw8F).
• When changing a value in Output time setting Y (RWw10 to RWw8F), set a time same as or later than the start timing of
the second synchronization cycle from the change. If an earlier time is set, the output does not change and an output
change disabled time setting error (error code: 0210H) occurs.
I/O module
 Assume that Time A is to be set for Output time setting Y0 (RWw10 to RWw13).
 The range of time that cannot be set as Time A
 The range of time that can be set as Time A
(1) Synchronization cycle
(2) Input
(3) Operation
(4) Output
(5) Time A
(6) Start timing of the second synchronization cycle from the setting
8 FUNCTIONS
170
8.3 CC-Link IE TSN Network Synchronous Communication Function
Scan program
Synchronization
control interrupt
(2) (3) (4)
program
Output time setting Y0
(RWw10 to RWw13)
(1)
(2) (3) (4)
Ò
Ó
(2) (3) (4)
Ô
(5)
(6)