■Operation
The following remote registers (RWr/RWw) are used for the output time setting control.
• ON/OFF selection flag (RWw4, RWw5) ( Page 241 ON/OFF selection flag)
• Output time setting Y (RWw10 to RWw8F) ( Page 244 Output time setting)
Ex.
The following figure shows the operation of output time setting control using the external output Y0.
Synchronization cycle
Output time setting Y0
(RWw10 to RWw13)
ON/OFF selection flag Y0
(RWw4.b0)
External output Y0
(status of Y0 terminal)
OFF
Performed by the I/O module
 The output turns on at DD:EE:FF.000, BB/CC/20AA.
 The output turns off at DD:EE:FF.010, BB/CC/20AA.
(1) 1 (Turn on the output.)
(2) 0 (Turn off the output.)
• For the I/O module operating with the output time setting control, External output signal Y (RY0 to RYF,
RY10 to RY1F) becomes invalid.
• A change of the external output Y (status of the Y terminal) is sent to the connected device with delay of
the maximum output response time.
• Therefore, if the output is set to turn on or off at an interval shorter than the maximum output response time,
the actual output may not turn on or off.
• The resolution of output time setting control is 8ns.
• The input change time to be stored in the buffer memory area is based on the clock of the network where
the I/O module performs data link. The clock of the network differs from the clock of the CPU module.
Therefore, set a time to turn on or off the output based on the input change time.
1595620800000000000
(20AA/BB/CC DD:EE:FF,000)
(1)
ON
Ò
8.3 CC-Link IE TSN Network Synchronous Communication Function
1595620800010000000
(20AA/BB/CC DD:EE:FF,010)
(2)
OFF
Ó
8 FUNCTIONS
8
169