Page 1
INVERTER Plug-in option PRE-OPERATION INSTRUCTIONS FR-E8DS E KIT INSTALLATION INSTRUCTION MANUAL CONNECTING THE 24 V EXTERNAL POWER SUPPLY 24 VDC input...
Page 2
Safety instructions Thank you for choosing this Mitsubishi Electric inverter plug-in option. This Instruction Manual provides handling information and precautions for use of this product. Incorrect handling might cause an unexpected fault. Before using this product, read all relevant instruction manuals carefully to ensure proper use.
Page 3
Injury Prevention CAUTION The voltage applied to each terminal must be as specified in the Instruction Manual. Otherwise an explosion or damage may occur. The cables must be connected to the correct terminals. Otherwise an explosion or damage may occur. ...
Page 4
General instruction For clarity, illustrations in this Instruction Manual may be drawn with covers or safety guards removed. Ensure all covers and safety guards are properly installed prior to starting operation.
— CONTENTS — Safety instructions 1 PRE-OPERATION INSTRUCTIONS Unpacking and checking the product..........................6 1.1.1 Product confirmation ................................6 1.1.2 SERIAL number check................................7 Component names ................................8 Specifications ..................................9 1.3.1 Input terminal specifications..............................9 1.3.2 Availability of the inverter functions while the 24 V external power is supplied..............9 2 INSTALLATION Pre-installation instructions ............................10 Installation procedure ..............................10...
PRE-OPERATION INSTRUCTIONS Unpacking and checking the product Take the plug-in option out of the package, check the product name, and confirm that the product is as you ordered and intact. This product is a plug-in option made for the FR-E800 series inverters. 1.1.1 Product confirmation Check the enclosed items.
1.1.2 SERIAL number check The FR-E8DS is available for the inverters manufactured in December 2021 or later. Check the SERIAL number printed on the rating plate or on the package of the inverter. Rating plate example Rating plate □□ ○○ ○...
Component names Front view Rear view Refer to Symbol Name Description page Used to fix this product to the inverter by inserting a mounting screw Mounting hole or a spacer. Terminal block Connected to a 24 V external power supply. Board mounted option connector Used to connect this product to the option connector of the inverter.
Specifications 1.3.1 Input terminal specifications Terminal symbol Common Terminal function description Rated specification Use the 24 V external power supply to turn ON/OFF I/O terminals, keep the operation panel ON, and carry out communication during Input voltage: 23.5 to 26.5 VDC communication operation even at power-OFF state of inverter's Input current: 0.7 A or less main circuit power supply.
INSTALLATION Pre-installation instructions Check that the inverter's input power and the control circuit power are both OFF. CAUTION • Do not install or remove this product while the inverter power is ON. Doing so may damage the inverter or this product. •...
Page 11
For the FR-E820-0175(3.7K) or lower, FR-E840-0170(7.5K) or lower, and FR-E860-0120(7.5K) or lower Remove the inverter front cover. (Refer to the FR-E800 Instruction Manual (Connection) for instructions to remove the cover.) Use a nipper or the like to cut off the bottom of the front cover for plug-in option. Ensure no burr is left.
Page 12
Remove the body screws of the inverter, then install the hexagon spacers to the inverter (tightening torque 0.56 to 0.75 N·m). Fit the junction connector, which has been connected to the plug-in option, to the guide of the option connector on the inverter, and insert the junction connector as far as it goes.
Page 13
For the FR-E820-0240(5.5K) or higher and FR-E840-0230(11K) or higher Remove the upper front cover and the lower front cover from the inverter. (Refer to the FR-E800 Instruction Manual (Connection) for instructions to remove the covers.) Use a nipper or the like to cut off the dummy cover of the lower front cover in order to install the option small cover. Upper front cover Dummy cover Ensure no burr is left.
Page 14
Remove the body screws of the inverter, then install the hexagon spacers to the inverter (tightening torque 0.56 to 0.75 N·m). Fit the junction connector, which has been connected to the plug-in option, to the guide of the option connector on the inverter, and insert the junction connector as far as it goes.
Page 15
Install the lower front cover to the inverter. 6. Plug-in option 5. Hexagon spacer 7. Mounting screw 10. Front cover 4. Junction connector for plug-in option 9. Recessed neck screw 7. Mounting screw 4. Straight spacer 10. Option small cover 11.
Page 17
NOTE • When the junction connector is installed to the plug-in option, the option is fixed with the hooks of the connector. The junction connector cannot be removed from the plug-in option. • When removing the front cover for plug-in option from the inverter, note that the recessed neck screw cannot be removed from the front cover for plug-in option.
Wiring For the wiring, strip off the sheath of a cable, and use it with a crimp terminal. For a single wire, strip off the sheath of the wire and apply directly. Insert the crimp terminal or the single wire into a socket of the terminal. Strip off the sheath as shown below.
Page 19
Crimp terminals commercially available (as of October 2020. The product may be changed without notice.) Cable Ferrule terminal model Crimping tool gauge Manufacturer With insulation Without name For UL wire sleeve insulation sleeve AI 0,34-10TQ — — AI 0,5-10WH — AI 0,5-10WH-GB 0.75 AI 0,75-10GY...
Page 20
Insert the cable into a socket. When using a single wire or stranded wires without a crimp terminal, push the open/close button all the way down with a flathead screwdriver, and insert the wire. Open/close button Flathead screwdriver • Wire removal Pull the wire while pushing the open/close button all the way down firmly with a flathead screwdriver.
Page 21
NOTE • When using stranded wires without a crimp terminal, twist enough to avoid short circuit with a nearby terminals or wires. • Pulling out the wire forcefully without pushing the open/close button all the way down may damage the terminal block. •...
CONNECTING THE 24 V EXTERNAL POWER SUPPLY Connect the 24 V external power supply across terminals +24 and SD to turn the I/O terminal ON/OFF operation, keep the operation panel ON, and carry out communication during communication operation even at power-OFF state of inverter's main circuit power supply.
Page 23
Confirming the 24 V external power supply input • The "24V DC" LED on the front cover for plug-in option is ON while the 24 V external power is supplied. When the main circuit power is turned OFF and the 24 V external power supply operation starts, "EV" blinks on the operation panel. Blinking •...
Page 24
• The output data is retained when "1 or 11" is set in Pr.495 Remote output selection. NOTE • Inrush current equal to or higher than the 24 V external power supply specification may flow at power-ON. Confirm that the power supply and other devices are not affected by the inrush current and the voltage drop caused by it.
CE marking. • The authorized representative in the EU The authorized representative in the EU is shown below. Name: Mitsubishi Electric Europe B.V. Address: Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany EMC Directive We declare that this product conforms with the EMC Directive when installed in a compatible inverter, and affix the CE marking on the packaging plate.
Year, and the Month is indicated by 1 to 9, X (October), Y (November), or Z (December). • Authorized sales representative (importer) in the CU area The authorized sales representative (importer) in the CU area is shown below. Name: Mitsubishi Electric (Russia) LLC Address: 52, bld 1 Kosmodamianskaya Nab 115054, Moscow, Russia Phone: +7 (495) 721-2070...
Appendix 3 Restricted Use of Hazardous Substances in Electronic and Electrical Products The mark of restricted use of hazardous substances in electronic and electrical products is applied to the product as follows based on the “Management Methods for the Restriction of the Use of Hazardous Substances in Electrical and Electronic Products”...
Appendix 4 Referenced Standard (Requirement of Chinese standardized law) This Product is designed and manufactured accordance with following Chinese standards. EMC: GB/T 12668.3 APPENDIX...
Appendix 5 Compliance with the UK certification scheme We declare that this product conforms with the related technical requirements under UK legislation when installed in a compatible inverter, and affix the UKCA (UK Conformity Assessed) marking on the packaging plate. Approval conditions are the same as those for the EU Directives.
REVISIONS *The manual number is given on the bottom left of the back cover. Revision date *Manual number Revision Oct. 2021 IB(NA)-0600958ENG-A First edition...
Page 32