9.5 Commissioning Fire Extinguishing Devices (CE)

9.5.1 Commissioning the Extinguishant Control Panel (CE)

Context
Initial configuration parameters have been set for the extinguishant control panel before
delivery and do not need to be set onsite.
Preparations
Tools: none
Documents: power supply and distribution system diagram, documents delivered with the
extinguishant control panel, fire extinguishing system conceptual diagram (CE), fire
extinguishing device layout diagram (CE)
Skill requirement: fire engineer
Procedure
Step 1 Switch on the input power circuit breaker of the extinguishant control panel or connect the
extinguishant control panel batteries to power on the extinguishant control panel.
Step 2 Flip the key to Enable Control rightward, and set the access level of the extinguishant
control panel to 2.
Step 3 Press Silence/Sound Alarm to start or abort the fire alarm bell.
Step 4 Press Alarm/Fault Warning Silence to silence the fault noise generated by the extinguishant
control panel.
Issue 02 (2017-01-10)
For the diagrams, see the initial configuration parameter manual for the solution in use.