FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
System
Fire
extinguishin
g system
(standard)
Issue 02 (2017-01-10)
Check Item
Content
Access
Container
control
door
system
power-on
commissioni
ng
Fire control
Indicators
panel
on the fire
control
panel
Alarm bell
Unlock
the fire
alarm
control
panel, and
press the
ALARM
BELL
button.
Smoke
Check the
detector
indicator.
Heat
Check the
detector
indicator.
Emergency
Check the
start/stop
indicator.
switch
Emergency
Check the
light
indicator.
Fire alarm
Check the
horn/strobe
alarm and
fault
Gas release
indicators
indicator
on the fire
alarm
Pressure
control
announciator
panel.
Electromagn
etic valve
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Check Standard
The electronic lock indicator is green
when the container door is closed.
The electronic lock indicator is red when
the container door is open.
The container door can be opened from
outside the container using an access card,
and door opening operations are logged in
the management system.
The container door can be opened from
inside the container using the exit button,
and door opening operations are logged in
the management system.
Indicators on the fire alarm control panel:
The power indicator is on.
The alarm indicators are off.
The alarm bell rings normally.
The indicator blinks once every 6 seconds.
The indicator blinks once every 6 seconds.
The run indicator is steady green.
The mains power indicator is steady green.
NOTE
The charge indicator turns on when the battery
voltage is low.
The alarm and fault indicators are off.