Huawei FusionModule1000B V100R003C00 Commissioning Manual page 93

Water-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
No.
Procedure
Step 1 Tap
Figure 9-6
Figure 9-6 Teamwork setting screen 1
Issue 02 (2017-01-10)
Option
> Teamwork Settings on the home screen to enter the screens shown in
and
Figure
9-7.
To change the teamwork settings, you need to log in as the Admin or Engineer user. For
the passwords, see the 30 kW chilled water precision air conditioner teamwork initial
configuration table.
Set the teamwork function on the teamwork setting screen. Parameters to be set for the
master device include Teamwork unit no., Teamwork unit address, Teamwork
function, Network, Total number of units, Number of running units, Standby mode
rotation, Rotation period, Rotation time, Forced rotation, Requirement control, and
Cascade. However, a slave device only supports parameters like Teamwork unit no.,
Teamwork unit address, and Teamwork function.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Remarks
Dark gray background color indicates that the device is
offline,
as shown in
9 Commissioning Core Components
.