FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
System
Cooling
system
Issue 02 (2017-01-10)
Check Item
Content
UPS
MDU
Chilled
Remote
water
temperatu
precision air
re and
conditioner
humidity
(T/H)
sensor
Main
control
board
Controller
Chiller
Output
function
Temperat
ure
settings
and
control
precision
Compone
nt layout
Settings
of other
functions
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Check Standard
The screen is free from erratic display or
missing characters.
Settings meet the requirements of the
current scenario.
The mains voltage, power, current, power
factor, electricity energy, and switch status
are properly displayed.
The branch current, electricity energy, and
switch status are properly displayed.
The communication between the MDU
and monitoring board is normal.
There is no active alarm whose severity is
higher than Minor. If there are any alarms,
record the alarms and handle them.
The indicator is on.
The DIP switch setting is the same as the
initial setting.
The DIP switch setting is the same as the
initial setting.
The screen is free from erratic display or
missing characters, and displays no alarm.
The teamwork setting is the same as the
initial setting.
All output functions are automatic.
The temperature settings and control precision
are appropriate.
All components are installed in the correct
positions.
Other functions are properly set.