FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
Specifications
SY16: DO1 output
SY23: extremum
interval
SY24: sliding
window time
Step 4 Set multi-rate parameters for the PD510 electricity meter.
Table 9-2 Multi-rate parameter settings for the PD510 electricity meter
Specifications
E01: multi-rate
enable
E02: default setting
enable
Step 5 Set alarm parameters for the PD510 electricity meter.
Table 9-3 Alarm parameter settings for the PD510 electricity meter
Specifications
ron: relay n
Type: alarm mode
Issue 02 (2017-01-10)
Factory
Setting
0
10
5
Factory
Setting
Enabled
Default
Factory
Setting
Set based on the
actual situation.
Default
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9 Commissioning Core Components
Remarks
Electricity output from the DO1 port. The value is
an integer ranging from 0 to 8.
0: no output association
1: consuming active electricity
2: releasing active electricity
3: absorbing reactive electricity
4: sending out reactive electricity
5: general active electricity
6: net value of active electricity
7: general reactive electricity
8: net value of reactive electricity
The interval for extremum statistics is 5-60 min.
Range: 1-60 min
Remarks
Enable or disable the multi-rate function.
The electricity meter has been set before delivery
because the time setting is complicated. You can
customize the settings and restore the default
settings as necessary.
Remarks
n = 0-8
Refer to the DO working type table provided
in
Table
9-4.
72