Huawei FusionModule1000B V100R003C00 Commissioning Manual page 40

Water-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
Syst
em
Cool
ing
syste
m
Issue 02 (2017-01-10)
Check
Operation Method
Item
Phase
Verify the phase sequences of
sequence
upstream and downstream power
distribution devices of the
FusionModule1000 using a phase
sequence meter.
Voltage
Measure the voltage at the ATS
input end using a multimeter.
Frequency
Measure the frequency at the ATS
input end using a multimeter.
Battery
Check the number of batteries.
Check battery connection.
Measure the battery cell
voltage using a multimeter.
Measure the battery string
voltage using a multimeter.
Phase
Verify that the L1, L2, L3, N, and
sequence of
PE wires are connected for the
indoor and
indoor and outdoor units in the
outdoor unit
correct phase sequence using a
cables
phase sequence meter.
Water refill
Check whether the water refill
for the air
valve is open, and whether the
conditioner
water refill pressure meets the
humidifier
requirement.
Water refill
Check whether the water refill
from the
valve is open, and whether the
automatic
water refill pressure meets the
water refill
requirement.
valve
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Items to Be Checked Before Power-On
Expected Result
The phase sequences are
consistent.
The voltage is in the range
of 342-456 V.
Frequency range for the 50
Hz scenario: 49-51 Hz
Frequency range for the 60
Hz scenario: 59-61 Hz
The batteries are correct in
quantity and intact.
Batteries are connected
based on the design
requirements and installed
securely. Battery electrodes
are correctly connected.
The voltage is within the
rated voltage range of
batteries. The battery string
voltage is the single battery
voltage multiplied by the
number of batteries.
The voltage measurement
result meets the
requirement of system
power backup.
The phase sequence is correct.
The water refill valve is open,
and the water refill pressure is
0.1-0.7 MPa.
The water refill valve is open,
and the water refill pressure is
greater than 0.15 MPa.
34