Huawei FusionModule1000B V100R003C00 Commissioning Manual page 96

Water-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
Step 2 Verify teamwork settings for each chilled water precision air conditioner by referring to the
30 kW chilled water precision air conditioner initial teamwork configuration table.
Verify teamwork settings for each 30 kW chilled water precision air conditioner before
starting the air conditioners.
If any setting is inconsistent with the initial setting, change it to the initial setting.
Step 3 View teamwork information. Tap
The teamwork information is displayed, as shown in
Figure 9-8 Teamwork information screen 1
Figure 9-9 Teamwork information screen 2
Issue 02 (2017-01-10)
Master/Slave and Active/Standby indicate the information of the current unit. Other information is
about the teamwork information of the group.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9 Commissioning Core Components
at the lower right corner of the teamwork home screen.
Figure 9-8
and
Figure
9-9.
90