Water-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
4.
5.
6.
7.
8.
Issue 02 (2017-01-10)
Figure 7-26 Manual gas release button
During the countdown, if you press the extinguishant abort button, the countdown stops.
If you rotate the extinguishant abort button clockwise again to reset the button, the
countdown restarts from zero.
Figure 7-27 Extinguishant abort button
After the 30s countdown ends, a driver signal is sent to the electrical actuator.
The electrical actuator ejector pops up to 11-mm long.
Reinstall the yellow protective cover, and reset the extinguishant abort button to the state when it is
not pressed down.
Reset the ejector of the electrical actuator.
Press Processor Reset on the extinguishant control panel to reset the panel.
Reinstall the electrical actuator on the container valve.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.