FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
The left and right figures respectively show the scenes before and after the panel is removed.
1.
2.
3.
4.
5.
6.
Step 10 Simulate a cable disconnection fault for a smoke detector or heat detector.
1.
2.
3.
4.
Zone 1 and 2 respectively indicate fault alarms for the smoke and heat detectors.
Issue 02 (2017-01-10)
Press RESET on the fire alarm control panel to reset the fire alarm control panel.
Set the fire alarm control panel to the AUTO state.
Press the START button to trigger a release signal to the fire alarm control panel. The
release countdown starts.
In the countdown period, if you press the STOP button, the countdown stops. If you
press the STOP button again, the countdown restarts.
After the countdown ends, the fire alarm control panel generates a solenoid valve driver
voltage.
Reset the green START button.
Press RESET on the fire alarm control panel to reset the fire alarm control panel.
Set the fire alarm control panel to the AUTO state.
Hold the body of the smoke or heat detector, and turn the detector body to separate it
from the base.
Figure 7-10 Removing the detector
Verify that the fire alarm control panel has reported a zone fault, as shown in
7-11.