Huawei FusionModule1000B V100R003C00 Commissioning Manual page 79

Water-cooled it solution
Table of Contents

Advertisement

FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
Specifications
Alar/pord: alarm
parameter
Alarm threshold
Tdly: Delay time
Puls/pdly: impulse
width
Table 9-4 DO working type
DO Name
DO1
DO2
DO3
DO4
DO5
DO6
Issue 02 (2017-01-10)
Factory
Setting
Default
Default
Default
Default
DO
Meaning
Working
Type
0
Not defined
9
Remote
control
10
Alarm:
If the
delay
11
time
equals 0,
the alarm
12
is a level
alarm.
13
If the
delay
time
14
does not
equal 0,
15
the alarm
is an
impulse
16
alarm.
17
18
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9 Commissioning Core Components
Remarks
-
-
-
-
Not defined
05H communication
control
Low: alarm; high:
clear
High: alarm; low:
clear
Low: alarm; high:
not clear
High: alarm; low:
not clear
Phase voltage low
alarm
Phase voltage high
alarm
Line voltage low
alarm
Line voltage high
alarm
Forcibly clear
alarms. The delay
time and pulse width
are still functional
during forcible
clearance.
Parameter
-
Alarm type, alarm
number, alarm
value, and alarm
impulse delay time
73