FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
Step 11 Press RESET to reset the fire alarm control panel.
Step 12 (Optional) Check whether the fire alarm signals are reported to the management system.
Step 13 Reconnect cables to the electromagnetic valve.
Figure 7-14 Connecting cables to the electromagnetic valve
Step 14 Remove the safety pin after verifying that the fire extinguishing system is working properly.
Issue 02 (2017-01-10)
Figure 7-13 Heat detector installation reference line
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 System Commissioning