FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
5.
Issue 02 (2017-01-10)
Figure 7-11 Fault alarms on the fire alarm control panel
Hold the smoke detector body, align the smoke detector indicator with the position
shown by (1) in
Figure
7-12, and turn the detector body clockwise to the position shown
by (2) in
Figure 7-12
to install the smoke detector.
Reinstall the heat detector in a similar way as reinstalling the smoke detector, as shown in
7-13.
After the smoke detector or heat detector is reinstalled, the corresponding fault indicator turns off in
about 3s.
Figure 7-12 Smoke detector installation reference line